Commercial · Three phase

IZ-240K-3P240 kW · 480 kWh

Floor-standing cabinet · Large MSME · IT park floor · 200-bed hospital · 5-star hotel

240 kW three-phase BESS cabinet for large MSME factories, IT-park floors, 200-bed hospitals, and 5-star hotels. High-voltage DC bus, hybrid solar input, full Infozeb EMS integration.

INFOZEB IZ-240K-3PRACK 01RACK 02RACK 03PCS
Phase
Three
DC Bus
200–1000 VDC
AC Output
440 V · 240 A/ph
Solar MPPT
320 kWp
Specification

Full technical sheet.

Battery

  • Cell chemistryLiFePO4
  • Cell spec3.2 V · 100 Ah
  • Pack configurationModular 5.12 kWh racks
  • Usable capacity480 kWh
  • DC bus voltage200–1000 VDC
  • Cycle life≥ 6,000 @ 80% DoD
  • Round-trip efficiency≥ 95%

Power conversion

  • TopologyBi-directional hybrid
  • Rated output240 kW
  • AC voltage3φ 440 V ±10%
  • Frequency50 Hz ±0.5 Hz
  • Solar input320 kWp · 4 MPPT
  • Grid-tied THD< 3%
  • Island transfer< 20 ms

Protection & safety

  • Cell-level fuseYes
  • BMS protectionsOV / UV / OC / OT / SC
  • Rack pyro-fuseYes
  • Gas detectionVOC + H₂
  • Fire suppressionAerosol
  • IP ratingIP54
  • Operating temp-20°C → 55°C

Communication & EMS

  • Local busCAN · RS485 · Modbus TCP
  • Cloud uplink4G LTE · Ethernet
  • EMS platformportal.infozeb.energy
  • Dispatch modesSelf-use · ToU · Peak shave
  • Anti-exportConfigurable
  • OTA firmwareBMS + PCS + EMS
  • APIREST + MQTT
Compatible applications

Where this size fits.

Peak-demand shaving

Clip maximum-demand peaks. 30–45% demand-charge reductions are typical on MSME and commercial sites.

Hybrid solar self-consumption

High-voltage DC bus matches 80–320 kWp commercial PV. Store midday generation for evening / night-shift consumption.

DG replacement + UPS

Replaces both an oversized DG set and a separate lead-acid UPS — one platform, one warranty, no diesel headaches.

Ready to size your site?

Tell us your load profile and grid limits. We'll respond with a quote and sizing proposal in one working day.